Control Board Overview
E-S 500 / 502 Classic Series Instruction Manual
5.5
!
CAUTION! Do not run 110V AC power direct to the
board. This will cause permanent damage to both
boards and void your warranty. Caution!
Gate Opener reactions to signals:
PUSH2 (PUSH 2 terminal and PUSH 2 button):
Details:
• Will activate gate with momentary contact (momentary contact between PUSH2
and V+).
• Controls both leaves in 2 leaf mode (Dip switch 2 in the ON position)..
Only opens the gate, never closes it.
Pause time is able to be re-set indefinitely if this terminal is continuously closed
through a non-momentary contact (a connection between PUSH2 and V+ that is
not released) Then the time will be reset and held until the connection between
PUSH2 and V+ is released - then it will count down the pause time and reclose.
Ideal for exit wand or exit loop.
Operational Sequence for terminal with autoclose ON (Dip switch 1 in on
position):
1. In closed position - momentary contact will open gates.
2. When opening - momentary contact will have no effect.
3. When stopped mid cycle from PUSH 1 or the Receiver - momentary
contact will open the gate.
4. When open with auto-reclose on - momentary contact will re-set pause
time and will start counting again after release of momentary contact. Closed
contact will continually re-set pause time and start counting down to reclose again
after contact is released.
5. When pause time countdown is stopped in open from a momentary contact of
PUSH 1 or the Receiver - momentary contact will have no effect.
6. When closing - momentary contact will re-open the gate.
Operational Sequence for terminal with autoclose OFF (Dip switch 1 in off
position):
1. In closed position - momentary contact will open gates.
2. When opening - momentary contact will have no effect.
3. When stopped mid cycle - momentary contact will open the gate.
4. When open with auto-reclose off - momentary contact will have no effect.
5. When closing - momentary contact will re-open the gate.
PUSH 1 and PUSH 2 these terminals can hold as many normally open connections as
needed, they will be wired in parallel. They are used for keypads, push buttons, universal
receivers, etc.